In order to operate any of PST's range of SST Zirconia O2 Sensors, you will require an interface board which provides the electronics necessary to power and control the zirconium dioxide oxygen sensors.
Alternatively, if you would rather have a complete solution, the OXY-FLEX Series or OEM O2 Measurement Solution may better suit your needs. When choosing the option you require, you should consider the following;
1. O2 measurement range: 0.1-25 % or 0.1-100 %
2. Output requirements: Digital (RS485 Modbus or RS232) or analogue (4-20mA or 0-10VDC)
3. Location: cable length is important to maintain the correct sensor heater voltage and minimize noise pick up, PST recommends keeping the cable length between the sensor and interface board as short as possible.
4. Convenience: do you want an “off-the-shelf” solution or configure the equipment yourself? If you want to design the board yourself. Please refer to our Zirconia Sensor Software and Hardware Design Guide.
There a number of options available which enable you to power and control SST’s range of zirconium dioxide O2 sensors; interface board or a complete solution. The following gives a brief overview of each type of interface PCB.
OXY-LC InterfaceThe OXY-LC Interface Board has a built-in pressure sensor for barometric pressure compensation and offers the following specifications. |
Supply voltage | 8 to 28VDC (RS485 variant) or 20 to 28VDC (analogue variants) |
O2 measurement range | 0.1 to 100 % (RS485 variant) and 0.1 to 25 % or 0.1 to 100 % (analogue variants) |
Operating temperature range | -30 ⁰C to +70 ⁰C |
Output options | RS485, 0-10V or 4 to 20mA |
Termination | PCB screw terminals |
O2I-Flex InterfaceThe O2I-FLEX has externally triggered automatic or manual calibration. Calibration can also be initiated via an on-board push button switch. The O2I-FLEX offers the following specifications. |
Supply voltage | 24VDC 10% |
O2 measurement range | 0.1 to 100 % (RS232 variant) and 0.1 to 25 % or 0.1 to 100 % (analogue variants) |
Operating temperature range | -10 ⁰C to +70 ⁰C |
Output options | RS232, 0-10V or 4 to 20mA |
Termination | Removable polarised screw terminals |
Complete OEM O2 Measurement SolutionThe Oxygen Measurement System has a built in pressure sensor for barometric pressure compensation and is used in combustion control including oil, gas and biomass boiler applications. |
Supply voltage | 8 to 28VDC (RS485 variant) or 20 to 28VDC (analogue variants) |
O2 measurement range | 0.1 to 100 % (RS485 variant) and 0.1 to 25 % or 0.1 to 100 % (analogue variants) |
Operating temperature range | -30 ⁰C to +70 ⁰C |
Output options | RS485, 0-10V or 4 to 20mA |
Termination | PCB screw terminals |
OXY-FLEX SeriesThe OXY-FLEX has externally triggered automatic or manual calibration and has an IP66 rated housing. A compact and cost effective zirconium-dioxide transmitter to measure percentage level oxygen in combustion processes, excess air monitoring, bakery ovens and many more applications. |
Supply voltage | 24VDC 10% |
O2 measurement range | 0.1 to 100 % (RS485 variant) and 0.1 to 25 % or 0.1 to 100 % (analogue variants) |
Operating temperature range (electronics) | -10 ⁰C to +85 ⁰C |
Gas temperature range (at probe tip) | 100 ⁰C to +250 ⁰C (standard variant), or -100 ⁰C to +400 ⁰C (high temp variant) |
Output options | RS232, 0-10VDC or 4 to 20mA |
Termination | Amphenol Ecomate C016 30C006 100 12 |
For more information on any of PST’s Zirconia O2 Sensors, interface electronics or complete oxygen sensing solutions, please contact us and to discuss your requirements.